The thermal withstand of a cable can be determined by comparing the maximum energy at the fault, with the maximum energy the cable can absorb.  The equation for this is:

I^2*t = k^2*A^2

"I^2*t" is proportional to the energy let-through of the protective device
       I - fault current, A
       t - fault duration, S

"k^2*A^2" is proportional to the energy withstand of the cable
        k - adiabatic constant
        A - cable cross-sectional area, mm2

To better understand the theory behind the above, please check The adiabatic equation.